Here is the cause of the hotel fire that resulted in the deaths of 78 people.

Here is the cause of the hotel fire that resulted in the deaths of 78 people.

17.05.2025 19:22

In the indictment prepared regarding the hotel fire in Kartalkaya, which claimed the lives of 78 people, prison sentences of up to 1998 years are requested for 13 individuals, while 19 individuals face sentences of up to 22 years and 6 months. The cause of the fire has also been confirmed. The indictment states that a short circuit occurred in the electric grill known as "grill plate," and that the flames from the device quickly spread to the LPG supply hose, causing the fire to grow rapidly.

```html

The public case was opened against 13 suspects, including the hotel owner and municipal officials, with a request for 1998 years of imprisonment, and for 19 suspects, a request for up to 22 years and 6 months in prison regarding the fire at the Grand Kartal Hotel in Bolu Kartalkaya.



INDICTMENT PREPARED FOR THE FIRE IN WHICH 78 PEOPLE LOST THEIR LIVES



The Bolu Chief Public Prosecutor's Office completed its indictment regarding the incident that occurred on January 21 at the Grand Kartal Hotel, where 78 people lost their lives and 133 were injured. The indictment states that the hotel owners, board members, and managers Halit Ergül, Emine Murtezaoğlu Ergül, Ceyda Hacıbekiroğlu, Elif Aras, Emir Aras, Zeki Yılmaz, Ahmet Demir, Kadir Özdemir, Cemal Özer, Mehmet Salun, as well as Bolu Municipality Deputy Mayor Sedat Gülener, Acting Fire Chief Kenan Coşkun, and Firefighter İrfan Acar are "responsible for the incident with possible intent."



Here is the cause of the hotel fire that claimed 78 lives


REQUEST FOR UP TO 1998 YEARS OF IMPRISONMENT FOR 13 PEOPLE



The indictment requests a total of up to 1998 years of imprisonment for 13 individuals for the crimes of "intentional killing with possible intent" and "intentional injury with possible intent" 78 times.



REQUEST FOR 22 YEARS AND 6 MONTHS OF IMPRISONMENT FOR 19 PEOPLE



In the indictment prepared by the Chief Public Prosecutor's Office, the technical personnel of the hotel Tahsin Pekcan, Hüseyin Özer, and Bayram Ütkü, kitchen staff Reşat Bölük, Enver Öztürk, and Faysal Yaver, occupational safety experts Kübra Demir and Ece Kayacan, reception officer Yiğithan Burak Çetin, officials of Mudurnu Energy Industry and Trade Inc. İbrahim Polat and İsmail Karagöz, FQC Global Certification Inc. official Ali Ağaoğlu and employee Aleyna Beşinci, LPG installation maintenance personnel Doğan Aydın and Muharrem Şen, Bolu Provincial Special Administration Secretary Sırrı Köstereli, Bolu Provincial Special Administration Deputy Secretary Bünyamin Bal, Bolu Provincial Special Administration License and Inspection Director Yeliz Erdoğan, and former Bolu Provincial Special Administration License and Inspection Director Mehmet Özel are requested to be punished with imprisonment of up to 22 years and 6 months for the crime of "causing the death and injury of multiple persons with conscious negligence."



Here is the cause of the hotel fire that claimed 78 lives


FILES OF TWO MINISTRIES SEPARATED



The indictment was sent to the Bolu Heavy Penal Court. Meanwhile, the files regarding the officials of the Ministry of Culture and Tourism and the Ministry of Labor and Social Security, for whom an investigation permit was requested, were separated from the current investigation due to the ongoing process.



"THE FIRE STARTED FROM THE 'GRILL PLATE' DEVICE"



According to the indictment, on the night of the incident, the hotel's breakfast chef Faysal Yaver turned on the electric grill called "grill plate" in the restaurant located on the fourth floor of the hotel. It was determined that the device, which remained on until the moment the fire started, did not function due to excessive corrosion of the thermostat in the middle of its 3 thermostats, and as a result, overheating occurred in the device.



Here is the cause of the hotel fire that claimed 78 lives


"THE SHORT CIRCUIT IN THE DEVICE STARTED THE FIRE"



Due to the heating in the device, a short circuit occurred due to wear and aging effects on the grill conductors. After the short circuit could not be eliminated by the circuit breaker protective elements, the fire started at 03:17 with a small flash from the "grill plate" device, referred to as "showroom," due to the evaporation and burning of animal fats in the grill section of the device.



"FLAMES SPREADING TO THE HOSE SUPPLYING LPG INCREASED THE FIRE"



The fire spread from the "grill plate" compartment to the nearby trash can and then to the hose supplying LPG at 03:24. As the flames melted the hose and ignited the LPG gas, the fire accelerated excessively, exceeding "controllable limits" at 03:26, and the color of the flames began to turn blue. Subsequently, the varnished OSB and wooden decorations used on the ceiling rapidly vaporized, causing excessive smoke and rapid burning.



Here is the cause of the hotel fire that claimed 78 lives


"THERE WAS NO GAS EXHAUST SYSTEM IN THE HOTEL"



The structure of the materials in the area where the fire first started and the fact that the kitchen staff left the door leading to the closed parking lot open for escape also accelerated the burning. Additionally, the inadequacy and faults in the stair and elevator structures, and the absence of a gas exhaust system caused flammable and toxic gases to rise rapidly to the upper floors of the hotel, filling all corridors with toxic smoke and flammable gases.



The "wooden paneling and coverings" among the structural elements of the building were also affected by the high temperatures and heat generated by the fire, while the window glasses exploded due to the sudden increase in ambient temperature, carrying the gases outside the building. This incident ignited the wooden cladding material on the exterior of the building, causing the flames to rise on the facade.



Here is the cause of the hotel fire that claimed 78 lives


"THE HOTEL'S EMERGENCY ACTION PLAN IS INSUFFICIENT"



"Although the fire issue was identified among emergencies for the hotel, the emergency action plan prepared was insufficient, the fire team and first aid team determined in the disaster management plan were composed of inadequate, inexperienced, and untrained individuals, the content of the emergency action plan was also insufficient, and due to the lack of fire training for the staff in the hotel, the staff did not know what to do, instead, they opened the main parking doors, which accelerated the fire, and there was no audible or visual automatic warning reaching the reception officer during the fire growth phase, thus the assigned personnel could not intervene in the fire and inadvertently engaged in behaviors that would accelerate the fire."

```Elbette, metni İngilizceye çevirebilirim. İşte çeviri:



```html

The indictment states that on the night of the fire, four staff members were working in the hotel kitchen to prepare breakfast, that the fire was first noticed at 03:24, that the staff member who noticed it informed the other staff, and then left the kitchen area. It was noted that the gendarmerie was called at 03:26 and the 112 Emergency Call Center was called on 03:27.

.

```



Eğer başka bir şeyle yardımcı olmamı isterseniz lütfen belirtin!